In the realm of electrical installations and maintenance, ensuring safety is paramount. Despite being a staple subject among professionals, distinguishing between 80% and 100% rated circuit breakers often poses challenges.
These ratings have significant implications for panel design within various industries, affecting decisions made by electrical original equipment manufacturers (OEMs), panel builders, contractors, and systems integrators. This article aims to elucidate the differences between these circuit breaker ratings and their practical applications.
Understanding Circuit Breaker Ratings in Panel Design
A continuous load is considered to be any load that may last for three hours or more
In the United States and Canada, the National Electric Code (NEC) outlines the distinctions between different circuit breaker ratings and their roles in panel design. According to NEC Section 210.20(A), a branch circuit breaker must be rated to accommodate both the non-continuous load and an additional 25% of the continuous load.
A continuous load is considered to be any load that may last for three hours or more. Consequently, panel designs typically require breakers that can support this extra 25% capacity, resulting in a preference for larger, and often more costly, breakers.
However, when a circuit breaker is rated to handle 100% of its capacity, the necessity for that additional 25% load margin disappears. Instead, such a breaker must efficiently manage the aggregate of both continuous and non-continuous loads.
Circuit Breaker Testing and Heat Dissipation
Due to the enclosed environments in which circuit breakers are typically installed, heat dissipation emerges as a crucial factor. To address this, heat rise tests are conducted to determine the maximum current a breaker can handle without exceeding allowable temperature limits.
This assessment involves comparing conventional free-air thermal current with conventional enclosed thermal current capabilities, ultimately influencing the rated operational current of the circuit breaker.
Manufacturers label breakers as either 80% or 100% based on their current-carrying capacities. An 80% rated breaker, pursuant to NEC section 210.20(A), indicates operation at 80% of its rating, suited for 80% branch circuit designs. Such breakers accommodate non-continuous loads and 125% of continuous loads. In contrast, a 100% rated breaker provides overcurrent protection matching the total of both load types.
NOARK Electric's M6 Series Offerings
NOARK Electric's M6 Series Molded Case Circuit Breakers are available in both 80% and 100% ratings, coming in capacities of 800A, 1000A, or 1200A. Offered in 3-pole or 4-pole configurations, they feature interrupting capacities of either 42kA or 65kA at 480Vac.
Termination options include Bus Bar or Lug Line/Load Side Connection. Manufactured under rigorous ISO and CIG 023 certifications, NOARK's low-voltage components adhere to stringent quality assurance standards.
NOARK's commitment to excellence is demonstrated through products that are tested and certified to meet top industry standards, all backed by a five-year limited warranty. This ensures both reliability and value for professionals reliant upon NOARK's solutions.
When it comes to electrical installations and maintenance, safety is of utmost importance. Even among professionals in the field, there is often a misunderstanding between 80% and 100% rated circuit breakers and their applications in panel design.
Electrical original equipment manufacturers (OEMs), panel builders, contractors, and systems integrators are all involved in making decisions about which circuit breaker should be installed to carry the load requirements of various given systems in many industries. This blog will clear up misconceptions between 80% and 100% circuit breakers and their applications in panel design.
First, let’s look at these terms and how they apply to electrical panel design. Please note, these terms apply to circuit breakers in the USA and Canada; consult the most recent applicable codes and standards in your region to comply with local laws.
Terms and How They Apply to Electrical Panel Design
In Canada and the United States, the National Electric Code (NEC) defines the difference between these terms and how the breaker ratings of a particular manufacturer will determine which circuit breaker can be used to fit the load of an electrical panel.
Section 210.20(A) of the NEC indicates that a circuit breaker for a branch circuit must be rated so that it can handle the non-continuous load plus 125% of the continuous load. A continuous load is one where the maximum current will continue for three hours or more. Therefore, when designing an electrical panel, the chosen breaker must be capable of having an additional 25% capacity of the continuous load above its manufacturer’s rating to accommodate this headroom.
Typically, this means selecting a larger and more expensive breaker. However, this is not always the case. With a 100% rated circuit breaker, the headroom required to accommodate the additional 25% capacity of the load is eliminated. In its place, the circuit breaker must be able to handle the sum of the continuous and the non-continuous load.
Understanding Circuit Breaker Tests and Ratings
Circuit breakers are typically installed in an enclosure where heat dissipation is poor compared to an open environment. Therefore, a heat rise test is done to determine the maximum current that the breaker can carry without a temperature rise in any part beyond the permissible limit. This means that a circuit breaker is rated for conventional free-air thermal current and conventional enclosed thermal current. The difference between free-air and enclosed thermal current capabilities affects the rated operational current of the circuit breaker.
Manufacturers differentiate between the current carrying capacities of circuit breakers of the same rating by putting either the 80% or 100% labels on their breakers. An 80% rated breaker means that the breaker is listed for operation at 80% of its rating and can be used in an 80% branch circuit design. The 80% design as per section 210.20(A) of the NEC provides overcurrent protection by considering the sum of the non-continuous loads and 125% of the continuous loads.
When a circuit breaker is listed for operation at 100% of its rating, the overcurrent protection device shall not be less than the sum of the continuous load and the non-continuous load.
Looking at NOARK Product Ratings
NOARK Electric’s M6 Series Molded Case Circuit Breaker has options for both 80% and 100% ratings. They are rated at 800A, 1000A, or 1200A, and are available in either 3-pole or 4-pole configurations. They have interrupting capacities of either 42kA or 65kA at 480Vac, and have Bus Bar or Lug Line/Load Side Connection termination points.
At NOARK, they manufacture low-voltage electrical components in plants that are certified according to ISO standards that satisfy the very highest demand in the field of quality assurance and production quality. In addition to ISO Certification, we also meet the stricter CIG 023 Certification for the purposes of covering the requirements of above-standard tests for local certification marks, which are always awarded by national certification authorities.
Rely on NOARK’s high-quality products and exceptional value, backed with world-class service and support. Every NOARK product is tested and certified to the highest industry standards and is covered by our exclusive five-year limited warranty.